"Power Factor Improvement:"

    When using power factor correction capacitors, the total KVAR on the load side of the motor controller should not exceed the value required to raise the no-load power factor to unity.
Over
correctiveness of this value may cause high transient voltages, currents, and torques that can increase safety hazards to personnel and possibly damage motor driven equipment.
    Never connect power factor correction capictors at motor terminals on elecvator motors, plugging or jogging applications, multi-speed motors or open transition, wye-delta, auto-transformer starting and some part-winding start motors.
    If possible, capacitors should be located at position 2 (Table 1.1). This does not change the current flowing through motor overload protectors. Connection of capacitors at position 3 requires a change of overload protectors. Capacitors should be located at position 1 for applications listed in paragraph 2 above. Be sure bus power factor is not increased above 95% under all loading conditions to avoid over excitation.

Table 1.1

Original
Power
Factor
Percent

Desired Power Factor Percent

 

100%

95%

90%

85%

80%

60%

1.333

1.004

0.849

0.713

0.583

62%

1.266

0.937

0.782

0.646

0.516

64%

1.201

0.872

0.717

0.581

0.451

66%

1.138

0.809

0.654

0.518

0.388

68%

1.078

0.749

0.594

0.458

0.328

70%

1.020

0.691

0.536

0.400

0.270

72%

0.964

0.635

0.480

0.344

0.214

74%

0.909

0.580

0.425

0.289

0.159

76%

0.855

0.526

0.371

0.235

0.105

78%

0.802

0.473

0.318

0.182

0.052

79%

0.776

0.447

0.292

0.156

0.026

80%

0.750

0.421

0.266

0.130

 

81%

0.724

0.395

0.240

0.104

 

82%

0.698

0.369

0.214

0.078

 

83%

0.672

0.343

0.188

0.052

 

84%

0.646

0.317

0.162

0.206

 

85%

0.620

0.291

0.136

 

 

86%

0.593

0.264

0.109

 

 

87%

0.567

0.238

0.083

 

 

89%

0.512

0.183

0.028

 

 

90%

0.484

0.155

 

 

 

91%

0.456

0.127

 

 

 

92%

0.426

0.097

 

 

 

93%

0.395

0.066

 

 

 

94%

0.363

0.034

 

 

 

95%

0.329

 

 

96%

0.292

 

97%

0.251

 

99%

0.143

 

    Assume Total plant load is 100 KW at 60% power factor. Capacitor KVAR rating necessary to improve power factor to 80% is found by multiplying KW (100) by the multiplier in table (0.583) which gives KVAR (58.3), nearest standard rating (60 KVAR) should be used.