Home • Welcome • Services • Industries • The 5 Steps • About Us • Equipment • Computing • Resource Library • Links • Web Articles • Contact Us • Search • Site Map

 
Download a copy of this document
Printer friendly version
Electrical
Ohm's Law:

R = Ohms
E = Volts
I = Ampere
W = Watts

Ohms = Volts / Amperes (R = (E / I)) 

Amperes = Volts / Ohms (I = (E / R))

Volts = Amperes x Ohms (E = IR)

Watts = Volts x Amperes (W = EI)

AC CIRCUITS POWER CALCULATIONS

EF = Efficiency

PF = Power Factor

KW = Kilowatts

HP = Horsepower

Ph = Phases1000

Watts = 1 KW

Efficiency =
746 x Output HP
Input Watts
3Ph KW =
Volts x Amps x PF x 1.732
1000
3Ph Amps =
      746 x HP     
1.732 x Eff. x PF

3Ph EF =
           746 x HP              
1.732 x Volts x Amps x PF
3Ph PF =
        Input Watts        
Volts x Amps x 1.732
1Ph-KW =
Volts x Amps x PF
1000
1Ph Amps =
      746 x HP     
Volts x Eff. x PF
1Ph EF =
        746 x HP       
Volts x Amps x PF
1Ph PF =
  Input Watts  
Volts x Amps
3 PhHP =
Volts x Amps x 1.732 x Eff. x PF
746
1Ph HP =
Volts x Amps x Eff. x PF
746

Related Items: 


©2005 Industrial Automation Systems. All rights reserved.